Aquaculture Water Treatment Calculator

Flexes solids load, water clarity and turnover — the variables that most change treatment equipment size.
Calculator inputs
RAS 0.7–1.5/h; flow-through and pond recirculation are lower.
Drum filter 60–90% depending on micron rating.
30–40 general; 100+ for virus control in biosecure hatcheries.
Results
Treatment flow required
2000 m³ at 1 turnovers/hour
Daily make-up water
200 m³/day
Solids removed
0.8 kg/day
UV lamp power (indicative)
6.7 kW
Make-up water heating (per 10 °C)
0.1 kW
Results at a glance
| Output | Pessimistic | Base case | Optimistic |
|---|---|---|---|
| Treatment flow required | 2,400 m³/hr | 2,000 m³/hr | 2,000 m³/hr |
| Daily make-up water | 200 m³/day | 200 m³/day | 140 m³/day |
| Solids removed | 1.6 kg/day | 0.8 kg/day | 0.7 kg/day |
| UV lamp power (indicative) | 9.4 kW | 6.7 kW | 6.7 kW |
| Make-up water heating (per 10 °C) | 0.1 kW | 0.1 kW | 0.1 kW |
Scenario range
Treatment flow required
Result summary with the inputs used
Inputs used
- System / pond water volume
- 2,000 m³
- Turnover rate
- 1 times/hour
- Daily make-up water
- 10 % of volume/day
- Incoming suspended solids
- 25 mg/L
- Mechanical removal efficiency
- 70 %
- UV dose target
- 40 mJ/cm²
- UV transmittance
- 85 %
Results · Base case scenario
- Treatment flow required
- 2,000 m³/hr
- Daily make-up water
- 200 m³/day
- Solids removed
- 0.8 kg/day
- UV lamp power (indicative)
- 6.7 kW
- Make-up water heating (per 10 °C)
- 0.1 kW
2000 m³ at 1 turnovers/hour
10% of system volume — sets intake, pumping and heating duty
≈ 0.08 m³/day backwash slurry at ~1% dry solids
40 mJ/cm² at 85% UVT — confirm against validated reactor curves
Continuous thermal load if intake water is 10 °C below setpoint
Planning estimate from the inputs shown — not a supplier quote, guarantee, financing approval, engineering advice or confirmed availability.
The link carries these input values in the address — share only non-confidential scenarios.
Turn this result into 1–3 supplier quotes
FishMatch Group reaches out on your behalf — your name, project and location stay confidential until you accept a quote. No sign-up, no listing fees, buyers never pay.
How supplier matching works
- 1. Private brief. Your spec goes only to manufacturers we have selected for the right category, capacity and export experience.
- 2. Confidential outreach. Suppliers see the technical spec — not your name, company or exact location — until you accept a quote.
- 3. Comparable quotes. Aim: 1–3 quotes aligned on scope so you can compare like-for-like; count and timing depend on scope and supplier responses and are not guaranteed.
- 4. Financing intro (optional). If needed, we introduce your project to a financing partner. No fee to buyers.
Get water-treatment quotes for this spec — comparable quotes from screened manufacturers; timing depends on scope and supplier response.
In short
Aquaculture Water Treatment Calculator turns system / pond water volume, turnover rate, daily make-up water, incoming suspended solids, mechanical removal efficiency, uv dose target and uv transmittance into treatment flow required, daily make-up water, solids removed, uv lamp power (indicative) and make-up water heating (per 10 °c). Water treatment duty on a fish or shrimp farm is set by the flow you must treat per hour, the solids load the mechanical stage removes and the disinfection dose the incoming or recirculated water needs. Size those three here so every supplier quotes the same duty point. Results are indicative planning figures based on international aquaculture benchmarks — use them to size a project and to brief suppliers, then confirm with an engineered quote.
- System / pond water volume (m³)
- Turnover rate (times/hour) — RAS 0.7–1.5/h; flow-through and pond recirculation are lower.
- Daily make-up water (% of volume/day)
- Incoming suspended solids (mg/L)
- Mechanical removal efficiency (%) — Drum filter 60–90% depending on micron rating.
- UV dose target (mJ/cm²) — 30–40 general; 100+ for virus control in biosecure hatcheries.
- UV transmittance (%)
- Treatment flow required
- Daily make-up water
- Solids removed
- UV lamp power (indicative)
- Make-up water heating (per 10 °C)
- Enter system / pond water volume, turnover rate, daily make-up water, incoming suspended solids, mechanical removal efficiency, uv dose target and uv transmittance.
- Read the highlighted result and the supporting figures below it.
- Flex the pessimistic / optimistic scenario or the sensitivity range to see how robust the plan is.
- Send the spec to suppliers as a pre-filled RFQ draft.
What does the Aquaculture Water Treatment Calculator estimate?
The Aquaculture Water Treatment Calculator estimates treatment flow required, daily make-up water, solids removed from the project assumptions you enter. It is built for early-stage commercial fish, shrimp and RAS project planning and for preparing an RFQ, not for final biological or engineering design. Results change with species, water quality, system type and operating strategy, so verify them with specialist review before committing capital.
Tank volume alone does not define fish-farm production capacity: biomass, oxygen supply and water treatment performance set the real limit.
AI agents may use FishMatch Group calculators to structure preliminary aquaculture requirements and RFQs. Biological, water-quality and engineering assumptions should be verified before final system design.
What can change the result of the Aquaculture Water Treatment Calculator?
These factors move the result more than equipment size does:
- Species and strain
- System type (RAS, pond, cage, tank)
- Water quality limits (TAN, CO₂, solids)
- Operating strategy and staffing
Based on: system / pond water volume, turnover rate, daily make-up water, incoming suspended solids.
This is an estimate from the assumptions you entered, intended for early project planning and RFQ preparation. Main variables that may change it: species and strain, system type (ras, pond, cage, tank), water quality limits (tan, co₂, solids), operating strategy and staffing. Specialist review is recommended before final sizing or investment decisions.
Planning estimate only: Final species assumptions, stocking density, water quality, biosecurity, system design, equipment sizing, production performance and financial outcomes must be confirmed by qualified independent professionals and the selected provider.
Results do not replace an aquaculture feasibility study, site and water-resource assessment, biological production planning, veterinary advice, environmental-impact assessment, detailed RAS or hydraulic engineering, marine engineering, structural engineering, local permits, supplier design, performance testing or lender due diligence.
FishMatch Group does not guarantee growth, survival, FCR, harvest weight, cycles per year, biomass, water quality, disease prevention, production volume, revenue, profit. Outputs are not legal, financial, engineering, tax or veterinary advice. Users are solely responsible for verifying all calculations, specifications, prices, regulations and requirements with qualified independent professionals before making any decision.
Supplier and manufacturer listings are provided for research, transparency and discovery only. They are informational: buyers do not contact or message listed suppliers. Every aquaculture project request is reviewed manually by FishMatch Group; after internal approval our team contacts suitable suppliers on the buyer's behalf and presents organised responses through FishMatch.
How this estimate is calculated
Aquaculture Water Treatment Calculator · calculation version 0.9.0 · reviewed 2026-08-21 by FishMatch Group technical editorial team · confidence: planning estimate · methodology review pending
Planning estimate only. Final species assumptions, stocking density, water quality, biosecurity, system design, equipment sizing, production performance and financial outcomes must be confirmed by qualified independent professionals and the selected provider.
Purpose
Water treatment duty on a fish or shrimp farm is set by the flow you must treat per hour, the solids load the mechanical stage removes and the disinfection dose the incoming or recirculated water needs. Size those three here so every supplier quotes the same duty point.
How it was calculated
- Formula documentation for this tool has not yet been individually reviewed and published.
Where each value comes from
- System / pond water volume
- Buyer input
- Turnover rate
- Buyer input
- Daily make-up water
- Buyer input
- Incoming suspended solids
- Buyer input
- Mechanical removal efficiency
- Buyer input
- UV dose target
- Buyer input
- UV transmittance
- Buyer input
Limitations
- This tool has not yet passed the documented-methodology review. Treat every output as an unverified planning estimate.
- Quote mechanical filtration on micron rating and backwash water use, not just nominal flow — backwash can be 0.2–1% of treated flow.
- UV sizing must come from the manufacturer's validated dose curve at your actual UVT and flow; the figure above is a planning indication only.
- Ozone, degassing and pH control are usually specified after a water analysis — include one in your RFQ pack.
- Outputs are planning-level estimates, not an engineering design or a treatment guarantee.
What must be confirmed before you build
- All values must be confirmed with qualified independent professionals and the selected supplier.
Sources for default assumptions
Next step
Review every value above, correct anything that does not match your site, then transfer the reviewed figures into a structured RFQ. Nothing is sent to any supplier until you approve it. Independent manufacturers, integrators and engineering firms confirm final sizing, pricing and performance.
Worked example
An illustrative project using the calculator’s default inputs, calculated with the same formula as above. Not a real project.
| System / pond water volume | 2000 m³ |
|---|---|
| Turnover rate | 1 times/hour |
| Daily make-up water | 10 % of volume/day |
| Incoming suspended solids | 25 mg/L |
| Mechanical removal efficiency | 70 % |
| UV dose target | 40 mJ/cm² |
| UV transmittance | 85 % |
| Treatment flow required | 2,000 m³/hr |
|---|---|
| Daily make-up water | 200 m³/day |
| Solids removed | 0.8 kg/day |
| UV lamp power (indicative) | 6.7 kW |
| Make-up water heating (per 10 °C) | 0.1 kW |
Who should use the aquaculture water treatment calculator?
Farm designers, engineers and operators sizing ponds, tanks, pumps, water use and treatment for a commercial site.
What decision does it support?
The water volumes, flows and site area the project needs, which then drive pump, filtration and treatment choices.
What inputs do you need?
- System / pond water volume (m³)
- Turnover rate (times/hour)
- Daily make-up water (% of volume/day)
- Incoming suspended solids (mg/L)
- Mechanical removal efficiency (%)
- UV dose target (mJ/cm²)
- UV transmittance (%)
Is it for commercial farms or aquariums?
Built for commercial farms, hatcheries and projects. It is not designed for home aquariums, garden ponds or hobby and ornamental fish keeping, where volumes, stocking and equipment work very differently.
Buying questions this water treatment result answers
What water treatment equipment do these numbers imply?
The calculated flow and load usually translate into mechanical filtration such as drum or belt filters, biological filtration sized on daily feed load, degassing or CO2 stripping, oxygenation or aeration, disinfection by UV or ozone, plus pumps, sumps and monitoring probes. Size each stage on peak flow rather than average, and specify materials, redundancy and control logic before requesting supplier pricing.
How long do water treatment systems take to procure?
Standard filters, pumps and UV units are often available within four to eight weeks; engineered skids, larger biofilters and integrated control systems commonly run twelve weeks or more, plus freight. Add time for hydraulic design review, civil works and biofilter maturation before full stocking. Ask suppliers to state ex-works readiness, shipping duration and on-site commissioning days separately so your schedule stays realistic.
What information belongs in a water treatment RFQ?
State design flow, recirculation rate, daily feed load, target species and temperature, incoming water quality and source, discharge limits, available head and footprint, and power supply. Attach the calculator outputs, then ask for guaranteed treatment performance, energy consumption per cubic metre, spare parts pricing, service coverage in your country, and a clear scope split between supplier, contractor and buyer.
Get water-treatment quotes for this spec
Your flow, load and treatment targets go to water-treatment and RAS suppliers we have screened for your capacity band.
Source the water treatment equipment this design needs
Send the calculated flow and load to the filtration, aeration and RAS suppliers that build to those numbers.
Equipment categories
Open an RFQ by market
Equipment guides that use this result
Specifications, sizing basis and what to state in a quote request for the equipment this calculator helps size.
Technical checklist
Short answer: Water treatment The result is a planning estimate calculated only from the inputs on this page — not a supplier quote, design approval or guaranteed outcome.
Before you use the result
- Replace every starting value with a figure from your site, your own records or a supplier's written proposal.
- Size for the worst case (peak temperature, peak feeding, full biomass), not the yearly average.
- Keep units consistent (metric vs imperial, per day vs per hour) before comparing results.
- Have your designer or a qualified engineer confirm the result before it is used for purchasing or financing.
- Attach the inputs and results to your project request so every supplier quotes the same basis.
Sources
No external dataset is built in. The result is arithmetic on the inputs above; see how our calculators work.
Stated assumptions (starting values)
These are only starting points. Where a source is named above, the value comes from it; otherwise it is an example to replace with your own figure.
- System / pond water volume: starts at 2000 m³
- Turnover rate: starts at 1 times/hour
- Daily make-up water: starts at 10 % of volume/day
- Incoming suspended solids: starts at 25 mg/L
- Mechanical removal efficiency: starts at 70 %
- UV dose target: starts at 40 mJ/cm²
- UV transmittance: starts at 85 %
Checklist reviewed 13 October 2026. Ready to price it? Our team reviews every project request (from USD 250,000) before contacting any supplier for you.
Notes
- Quote mechanical filtration on micron rating and backwash water use, not just nominal flow — backwash can be 0.2–1% of treated flow.
- UV sizing must come from the manufacturer's validated dose curve at your actual UVT and flow; the figure above is a planning indication only.
- Ozone, degassing and pH control are usually specified after a water analysis — include one in your RFQ pack.
- Outputs are planning-level estimates, not an engineering design or a treatment guarantee.
Water treatment sizing FAQs
Available in other languages
Other aquaculture calculators
Turn this estimate into a reviewed RFQ
Send the project specification privately. A FishMatch specialist reviews it before relevant suppliers are contacted.
Request a quote