Battery Storage Sizing Calculator

Aquaculture critical loads — oxygenation, biofilter pumps, alarms — cannot tolerate outages. This tool sizes an LFP battery bank in kWh from critical-load kW, autonomy hours and depth-of-discharge (DoD).
Battery Storage Sizing Calculator — Solar panels and backup generator at a fish farm

Flexes load, autonomy, DoD, inverter efficiency and installed cost.

Calculator inputs

Example — use the depth of discharge in the battery datasheet and warranty

Example — use the inverter datasheet; PVWatts defaults to 96%

Example — use your installer's quote; compare with NREL's battery storage cost projections

Results

Battery nameplate

120.2 kWh

LFP, DoD 85%

Usable energy required

102.1 kWh

Estimated CAPEX

$54,068

Results at a glance

OutputPessimisticBase caseOptimistic
Usable energy required151.3 kWh102.1 kWh76.6 kWh
Battery nameplate197.8 kWh120.2 kWh85.8 kWh
Estimated CAPEX$97,932$54,068$34,758

Scenario range

Battery nameplate

PessimisticBaseOptimistic

Result summary with the inputs used

Inputs used

Critical load
12 kW
Autonomy required
8 hours
Usable DoD
0.85 0–1
Inverter efficiency
0.94 0–1
Installed cost
450 $/kWh

Results · Base case scenario

Usable energy required
102.1 kWh
Battery nameplate
120.2 kWh

LFP, DoD 85%

Estimated CAPEX
$54,068

@ $450/kWh installed

Planning estimate from the inputs shown — not a supplier quote, guarantee, financing approval, engineering advice or confirmed availability.

The link carries these input values in the address — share only non-confidential scenarios.

Turn this result into 1–3 supplier quotes

Send this spec privately to selected manufacturers.

FishMatch Group reaches out on your behalf — your name, project and location stay confidential until you accept a quote. No sign-up, no listing fees, buyers never pay.

How supplier matching works

  1. 1. Private brief. Your spec goes only to manufacturers we have selected for the right category, capacity and export experience.
  2. 2. Confidential outreach. Suppliers see the technical spec — not your name, company or exact location — until you accept a quote.
  3. 3. Comparable quotes. Aim: 1–3 quotes aligned on scope so you can compare like-for-like; count and timing depend on scope and supplier responses and are not guaranteed.
  4. 4. Financing intro (optional). If needed, we introduce your project to a financing partner. No fee to buyers.

In short

Battery Storage Sizing Calculator turns critical load, autonomy required, usable dod, inverter efficiency and installed cost into usable energy required, battery nameplate and estimated capex. Aquaculture critical loads — oxygenation, biofilter pumps, alarms — cannot tolerate outages. This tool sizes an LFP battery bank in kWh from critical-load kW, autonomy hours and depth-of-discharge (DoD). Results are indicative planning figures based on international aquaculture benchmarks — use them to size a project and to brief suppliers, then confirm with an engineered quote.

What you enter
  • Critical load (kW)
  • Autonomy required (hours)
  • Usable DoD (0–1) — Example — use the depth of discharge in the battery datasheet and warranty
  • Inverter efficiency (0–1) — Example — use the inverter datasheet; PVWatts defaults to 96%
  • Installed cost ($/kWh) — Example — use your installer's quote; compare with NREL's battery storage cost projections
What you get back
  • Usable energy required
  • Battery nameplate
  • Estimated CAPEX
How to use it
  1. Enter critical load, autonomy required, usable dod, inverter efficiency and installed cost.
  2. Read the highlighted result and the supporting figures below it.
  3. Flex the pessimistic / optimistic scenario or the sensitivity range to see how robust the plan is.
  4. Send the spec to suppliers as a pre-filled RFQ draft.

What does the Battery Storage Sizing Calculator estimate?

The Battery Storage Sizing Calculator estimates usable energy required, battery nameplate, estimated capex from the project assumptions you enter. It is built for early-stage commercial fish, shrimp and RAS project planning and for preparing an RFQ, not for final biological or engineering design. Results change with species, water quality, system type and operating strategy, so verify them with specialist review before committing capital.

Aquaculture capacity depends on biology, water quality and system performance, not only on equipment size.

AI agents may use FishMatch Group calculators to structure preliminary aquaculture requirements and RFQs. Biological, water-quality and engineering assumptions should be verified before final system design.

What can change the result of the Battery Storage Sizing Calculator?

These factors move the result more than equipment size does:

  • Species and strain
  • System type (RAS, pond, cage, tank)
  • Water quality limits (TAN, CO₂, solids)
  • Operating strategy and staffing
Preliminary planning result

Based on: critical load, autonomy required, usable dod, inverter efficiency.

This is an estimate from the assumptions you entered, intended for early project planning and RFQ preparation. Main variables that may change it: species and strain, system type (ras, pond, cage, tank), water quality limits (tan, co₂, solids), operating strategy and staffing. Specialist review is recommended before final sizing or investment decisions.

Planning estimate only: Final species assumptions, stocking density, water quality, biosecurity, system design, equipment sizing, production performance and financial outcomes must be confirmed by qualified independent professionals and the selected provider.

Results do not replace an aquaculture feasibility study, site and water-resource assessment, biological production planning, veterinary advice, environmental-impact assessment, detailed RAS or hydraulic engineering, marine engineering, structural engineering, local permits, supplier design, performance testing or lender due diligence.

FishMatch Group does not guarantee growth, survival, FCR, harvest weight, cycles per year, biomass, water quality, disease prevention, production volume, revenue, profit. Outputs are not legal, financial, engineering, tax or veterinary advice. Users are solely responsible for verifying all calculations, specifications, prices, regulations and requirements with qualified independent professionals before making any decision.

Supplier and manufacturer listings are provided for research, transparency and discovery only. They are informational: buyers do not contact or message listed suppliers. Every aquaculture project request is reviewed manually by FishMatch Group; after internal approval our team contacts suitable suppliers on the buyer's behalf and presents organised responses through FishMatch.

How this estimate is calculated

Battery Storage Sizing Calculator · calculation version 0.9.0 · reviewed 2026-08-21 by FishMatch Group technical editorial team · confidence: planning estimate · methodology review pending

Planning estimate only. Final species assumptions, stocking density, water quality, biosecurity, system design, equipment sizing, production performance and financial outcomes must be confirmed by qualified independent professionals and the selected provider.

Purpose

Aquaculture critical loads — oxygenation, biofilter pumps, alarms — cannot tolerate outages. This tool sizes an LFP battery bank in kWh from critical-load kW, autonomy hours and depth-of-discharge (DoD).

How it was calculated

  • Formula documentation for this tool has not yet been individually reviewed and published.

Where each value comes from

Critical load
Buyer input
Autonomy required
Buyer input
Usable DoD
Buyer input
Inverter efficiency
Buyer input
Installed cost
Buyer input

Limitations

  • This tool has not yet passed the documented-methodology review. Treat every output as an unverified planning estimate.
  • Performance source: NREL PVWatts v8 (developer.nlr.gov API, NSRDB PSM v3 weather), 1 kWp, standard module, fixed tilt at latitude, 14% losses, run 7 Oct 2026; defaults explained in Dobos, A.P., PVWatts Version 5 Manual, NREL/TP-6A20-62641 (2014) — 14% total losses, 96% nominal inverter efficiency.
  • Battery cost benchmark: Cole, W., Ramasamy, V., Turan, M., Cost Projections for Utility-Scale Battery Storage: 2023 Update, NREL/TP-6A40-85332 (2023); use your installer's quote first.
  • Round up to the battery module size your supplier offers.
  • For grid-tied hybrid systems, size to critical loads only — non-critical loads run on grid or solar directly.

What must be confirmed before you build

  • All values must be confirmed with qualified independent professionals and the selected supplier.

Sources for default assumptions

Next step

Review every value above, correct anything that does not match your site, then transfer the reviewed figures into a structured RFQ. Nothing is sent to any supplier until you approve it. Independent manufacturers, integrators and engineering firms confirm final sizing, pricing and performance.

Worked example

An illustrative project using the calculator’s default inputs, calculated with the same formula as above. Not a real project.

Inputs
Critical load12 kW
Autonomy required8 hours
Usable DoD0.85 0–1
Inverter efficiency0.94 0–1
Installed cost450 $/kWh
Result
Usable energy required102.1 kWh
Battery nameplate120.2 kWh
Estimated CAPEX$54,068
Power and energy

Who should use the battery storage sizing calculator?

Farm owners and engineers sizing grid, generator, solar or battery supply for pumps, aerators and other farm loads.

What decision does it support?

What power capacity and energy cost the farm should plan for, and whether backup or solar is worth quoting.

What inputs do you need?

  • Critical load (kW)
  • Autonomy required (hours)
  • Usable DoD (0–1)
  • Inverter efficiency (0–1)
  • Installed cost ($/kWh)

Is it for commercial farms or aquariums?

Built for commercial farms, hatcheries and projects. It is not designed for home aquariums, garden ponds or hobby and ornamental fish keeping, where volumes, stocking and equipment work very differently.

Technical checklist

Short answer: Battery kWh The result is a planning estimate calculated only from the inputs on this page — not a supplier quote, design approval or guaranteed outcome.

Before you use the result

  • Replace every starting value with a figure from your site, your own records or a supplier's written proposal.
  • Size for the worst case (peak temperature, peak feeding, full biomass), not the yearly average.
  • Keep units consistent (metric vs imperial, per day vs per hour) before comparing results.
  • Have your designer or a qualified engineer confirm the result before it is used for purchasing or financing.
  • Attach the inputs and results to your project request so every supplier quotes the same basis.

Sources

  • Performance source: NREL PVWatts v8 (developer.nlr.gov API, NSRDB PSM v3 weather), 1 kWp, standard module, fixed tilt at latitude, 14% losses, run 7 Oct 2026; defaults explained in Dobos, A.P., PVWatts Version 5 Manual, NREL/TP-6A20-62641 (2014) — 14% total losses, 96% nominal inverter efficiency.

Stated assumptions (starting values)

These are only starting points. Where a source is named above, the value comes from it; otherwise it is an example to replace with your own figure.

  • Critical load: starts at 12 kW
  • Autonomy required: starts at 8 hours
  • Usable DoD: starts at 0.85 0–1
  • Inverter efficiency: starts at 0.94 0–1
  • Installed cost: starts at 450 $/kWh

Checklist reviewed 13 October 2026. Ready to price it? Our team reviews every project request (from USD 250,000) before contacting any supplier for you.

Notes

  • Performance source: NREL PVWatts v8 (developer.nlr.gov API, NSRDB PSM v3 weather), 1 kWp, standard module, fixed tilt at latitude, 14% losses, run 7 Oct 2026; defaults explained in Dobos, A.P., PVWatts Version 5 Manual, NREL/TP-6A20-62641 (2014) — 14% total losses, 96% nominal inverter efficiency.
  • Battery cost benchmark: Cole, W., Ramasamy, V., Turan, M., Cost Projections for Utility-Scale Battery Storage: 2023 Update, NREL/TP-6A40-85332 (2023); use your installer's quote first.
  • Round up to the battery module size your supplier offers.
  • For grid-tied hybrid systems, size to critical loads only — non-critical loads run on grid or solar directly.

Battery kWh FAQs

Usable energy = critical load (kW) × autonomy hours ÷ inverter efficiency; nameplate capacity is that figure divided by usable depth of discharge. Sizing against critical life-support load rather than total farm load keeps the bank affordable.

Anything whose loss kills stock within hours: oxygenation and aeration, biofilter and recirculation pumps, and the monitoring and alarm system. Lights, offices, processing and cold storage can normally ride through an outage.

Lithium iron phosphate tolerates deep daily cycling, handles heat better than most alternatives and supports 80–90% depth of discharge, so nameplate capacity is close to usable capacity. Lead-acid needs roughly twice the nameplate for the same usable energy.

Other aquaculture calculators

Turn this estimate into a reviewed RFQ

Send the project specification privately. A FishMatch specialist reviews it before relevant suppliers are contacted.

Request a quote
Is FishMatch right for your project?

When is FishMatch a good fit for a buyer?

FishMatch can be a fit when a buyer needs structured RFQ intake, aquaculture-specific calculators, project-specific technical information and a clearer procurement path for battery kwh and the wider aquaculture project it belongs to. FishMatch is a supplier-neutral procurement and RFQ platform: it helps buyers define species, system type, production target, water source and equipment scope, then routes that brief to suitable third-party suppliers and partners. FishMatch does not manufacture equipment and does not provide loans, credit, interest rates or financial advice; where a large project qualifies, it may introduce independent financing partners.

Best for

  • ·Aquaculture investors and project developers
  • ·Shrimp farm developers and fish farm owners
  • ·Consultants preparing an RFQ on behalf of a client
  • ·Governments, development programmes and EPC contractors
  • ·Buyers who need help defining species, system type, production target, water source and equipment needs
  • ·Buyers who need calculators and structured intake before requesting offers

Not ideal for

  • ·Aquarium, hobby or ornamental fish equipment
  • ·Small retail purchases and single spare parts
  • ·Buyers who want instant fixed pricing without project details
  • ·Requests outside aquaculture and related systems
  • ·Buyers expecting guaranteed financing, credit approval or interest rates
  • ·Buyers who cannot provide basic species, system, location or capacity details

Short answer

How do you size and cost Battery Storage?

Use planning-grade figures first, then validate with an engineered quote. The Battery Storage model on this page converts your project inputs into indicative sizing and cost figures based on international aquaculture benchmarks. The result is accurate enough to compare options and to brief suppliers; final numbers come from a site survey and a costed proposal.

Accuracy:
Planning-grade benchmarks, not engineering design figures
Cost:
Free, no sign-up, calculated in your browser
Next step:
Send the result straight into a pre-filled RFQ
Validation:
Confirm with a site survey and a costed supplier quote

Before you request quotes

Costs & budgeting

How much does a commercial fish farm cost to build?

Budget ranges depend on system type, not on country alone. Pond and cage projects are usually the lowest capital per tonne of annual output, while recirculating (RAS) projects carry the highest equipment and energy share because filtration, oxygenation and backup power are mandatory. Reliable numbers come from a sized bill of quantities — species, target tonnage, water source and grow-out temperature — not from a generic price list. Use the FishMatch calculators to size the project, then submit an RFQ so quotes are priced against the same specification.

What drives the price differences between aquaculture equipment quotes?

Most spread between quotes comes from scope, not from margin: included spares, installation and commissioning, control and automation level, materials (HDPE vs steel vs FRP), certification and testing, delivery terms (EXW vs CIF) and warranty length. Two quotes are only comparable when they answer the same specification. A structured RFQ fixes the scope so differences reflect real engineering choices.

What operating costs should a business plan include?

Feed is normally the largest recurring cost, followed by energy (highest in RAS), labour, fingerlings or post-larvae, health management, water treatment consumables and maintenance. Financing cost and working capital for the first production cycle are frequently underestimated. FishMatch cost tools separate CAPEX from OPEX so the payback assumption is visible rather than implied.